Three phase Epoxy Encapsulated Transformer 413-1237-000 is an isolation transformer with primary and secondary windings that are physically separated from each other. It allows AC power to be taken from one device and fed into another without electrically connecting the two circuits. The transformer blocks transmission of DC currents but allow AC signals to pass. It is sealed in silica sand and resin solid mass, completely enclosing and protecting the core and coil, while significantly reducing audible noise and suitable for hazardous environments.

Preliminary General Drawing. (Dimension, inch).
*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.
Epoxy Encapsulated Transformer 413-1237-000 Winding Schematics:

| Product Type | Epoxy Encapsulated Transformer |
|---|---|
| Phase | Three |
| Power Rating | 75 kVA |
| Frequency, Hz | 60 |
| Vector Group | Delta-Delta(Dd0) |
| Primary voltage | 480 Volt |
| Primary Max Current, Amps | 120.3A |
| Primary Terminals | H1-H2-H3 |
| Primary Terminal Lugs | 2-14 AWG |
| Primary Voltage Taps | 0%; ±5.0% |
| Secondary Voltage | 240Δ/120 Volt Aux |
| Secondary Max Current, Amps | 251.0A |
| Secondary Terminals | X1-X2-X3 |
| Secondary Terminal Lugs | 2-14 AWG |
| Winding Conductor | Aluminum |
| Temperature Rise, °C | 130 |
| Insulation Class | 180 (H) |
| Insulation Level, (B.I.L), kVA | 10 |
| Efficiency at 35% Load, % | n/a |
| ANSI/IEEE Impedance, % | 4.0-5.0 |
| Sound Level, dB | 40 |
| Standards, Certifications, Compliances: | Meets NEMA ST-20, IEEE C57.12.01., IEEE C57.12.91, Seismic Qualified SDS=1.60g 2/h=1.0 OSHPD OSP-0109-10.,, cUL Listed. |
| Enclosure Type | Nema 3R. Outdoor Non-Ventilated Weather resistant steel enclosure (IP54) |