The frequency of large interconnected power distribution systems is tightly regulated so that, over the course of a day, the average frequency is maintained at the nominal value within a few hundred parts per million. While this allows simple electric clocks, relying on synchronous electric motors, to keep accurate time, the primary reason for accurate frequency control is to allow the flow of alternating current power from multiple generators through the network to be controlled.
Frequency of the system will vary as load is added to the system or as generators are shut down; other generators are adjusted in speed so that the average system frequency stays nearly constant. During a severe overload caused by failure of generators or transmission lines, the power system frequency will decline. Loss of an interconnection carrying a large amount of power (relative to system total generation) will cause system frequency to rise. Special protection relays in the power system network sense the decline and may automatically initiate load shedding or tripping of interconnection lines, to preserve the operation of at least part of the network. Quite small frequency deviations, on the order of 0.5 Hz on a 50 Hz or 60 Hz network, will result in automatic load shedding or other control actions to restore system frequency. Smaller power systems, not extensively interconnected with many generators and loads, may not maintain frequency with the same degree of accuracy.